AEMC 2130.32 6555 10,000V/15,000V Megohmmeters

(No reviews yet) Write a Review
SKU:
2130.32
UPC:
6.85338E+11
MPN:
2130.32
Availability:
1 - 2 week lead time
Weight:
25.00 LBS
Shipping:
Calculated at Checkout
$6,650.00
Frequently bought together:

Description

datasheet.png      usermanual.png

 

AEMC 2130.32 6555 10,000V/15,000V Megohmmeters

The Megohmmeter Model 6555 is a high-end portable measuring instrument intended for the measurement of a wide variety of electrical insulation resistance values on cables and devices operating at high voltage. It is the only fully automated 15,000V graphical insulation tester. The Model 6555 is packaged in a rugged case that is IP65 when closed. Test results and configuration information is provided on a graphical LCD screen as well as exportable through the use of DataView software provided. This megohmmeter can operate on battery or AC power while testing.

Features

  • Detection and measurement of input voltage, frequency, and current prior to running a test
  • Measurements at a fixed test voltage of 500, 1000, 2500, 5000, 10,000 or 15,000VDC
  • Measurements at an adjustable test voltage between 40 and 15,000VDC
  • Ramp voltage measurements with a ramp from 40 to 1100V or from 500 to 15,000V
  • Step voltage measurements with steps from 40 to 15,000V
  • Non-destructive (Early break) test, test stopped at a preset current (Break at I-limit) or Burn mode with no predefined stop point
  • Digital filtering of insulation measurements
  • Live measurement of the voltage to warn the operator of potential unsafe conditions
  • Programmable thresholds to trigger audible
  • Timed measurement duration checks
  • Fuse protection with display indication of defective fuse condition
  • Stores up to 80,000 measurements
  • Optically-isolated USB communication for transfer onto PC and report generation with the included DataView software

Application

  • Acceptance testing and preventive maintenance
  • Test motors, pumps, valves, cables, switchgears and electrical wiring installations
  • Continuity checks
  • High resistance or absorption tests
  • Spot reading tests
  • Timed resistance measurements
  • Dielectric Absorption Ratio (DAR) and Polarization Index (PI) tests
  • Multi-layer insulation testing (DD)
  • Test old or water damaged installations over long time periods
  • Motor insulation resistance measurements

Manual 1 Manual 2 Manual 3

View AllClose

Additional Information

Insulation Test Voltage 50V:
10kΩ to 2000GΩ (2TΩ)
Insulation Tests 100V:
10kΩ to 4000GΩ (4TΩ)
Insulation Tests 250V:
10kΩ to 10,000GΩ (10TΩ)
Insulation Tests 500V:
10kΩ to 15,000GΩ (15TΩ)
Insulation Tests 10,000V:
10kΩ to 25,000GΩ (25TΩ)
Insulation Tests 15,000V:
10kΩ to 30,000GΩ (30TΩ)
Insulation Tests Fixed Test Voltages:
500/1000/2500/5000/ 10,000/15,000V
Insulation Tests Variable Voltages:
Variable: 40 to 15kV Three user programmable voltage schemes
Insulation Tests Ramp Mode:
Programmable ramps: start voltage/end voltage/duration
Insulation Tests Ramp Configuration Range:
40 to 1100V/500 to 15,000V
Insulation Tests Step Mode:
Up to 10 steps (voltage and duration configurable for each step)
Insulation Tests Voltage Measurement After Test:
0 to 2500Vac; 0 to 4000Vdc
Insulation Tests Capacitance Measurement:
0.05 to 9.999μF/10.00 to 49.99μF
Insulation Tests Leakage Current Measurement:
0 to 8mA
Insulation Tests Discharge After Test:
Yes/Automatic
Insulation Tests Additional Test Stop Modes:
.
Insulation Tests I-Lim:
Programmable: 0.2 to 5mA
Insulation Tests Early-Break:
di/dt
Insulation Tests Timer:
Up to 99 minutes 59 seconds
Insulation Tests Burn Mode:
Constant testing
Insulation Tests Ratio Calculation:
PI, DAR, DD
Insulation Tests Calculation of R at ref. T°:
Yes
Insulation Tests Measurement Display Filter:
3 filters with 3 possible time-constants
Insulation Tests Graphs on Display:
R(t)+V(t); I(t); I(V)
Insulation Tests Storage:
256 registers, stores 80,000 points: R, V, I and date
Insulation Tests Communication:
USB optically-isolated port
Insulation Tests PC Software:
DataView®
Insulation Tests Power Supply:
NiMH rechargeable batteries, two 9.6V 4Ah battery packs charging by external voltage: 90 to 260V; 50/60Hz
Insulation Tests Battery Charging:
Battery charging allowed while performing insulation measurements
Insulation Tests Electrical Safety:
1000V CAT IV; IEC61010-1 and IEC 61557
Insulation Tests EMC, Mechanical Protection,Altitude:
EN 61326-1, IP54, 3000m
Insulation Tests Dimensions / Weight:
13.39 x 11.81 x 7.87 (340 x 300 x 200mm)/approx. 6.2kg (13.7lb)"