AEMC
AEMC 2141.01 6416 Clamp-On Ground Resistance Testers
- SKU:
- 2141.01
- UPC:
- 6.85338E+11
- MPN:
- 2141.01
- Availability:
- 1 - 2 week lead time
- Weight:
- 3.00 LBS
- Shipping:
- Calculated at Checkout
Frequently bought together:
Description
AEMC 2141.01 6416 Clamp-On Ground Resistance Testers
The Ground Resistance Tester Model 6416 measures ground rod and grid resistance and impedance without the use of auxiliary rods. Clamp-on ground resistance testers can be used in multi-grounded systems without disconnecting or de-energizing the ground system under test it. The Model 6416 simply clamps around the grounding electrode or conductor and measures the resistance to ground. By performing measurements on intact ground systems, the user also verifies the quality of the grounding connections and bonds. Resistance and continuity of grounding loops around pads and buildings may also be measured.
Features
- Touch voltage is displayed to alert user to potential unsafe conditions
- Large multi-function, bright yellow organic display (OLED) is visible in all lighting conditions
- Selectable test frequency improves accuracy in inductive environments
- Differentiates between loop and ground resistance measurements.
- Data storage (Ω, A,V and µH with time-stamping): Stores up to 300 measurements
- Easy clamp opening via a force compensation trigger system with 35mm clamp diameter
Applications
- Ground electrode system resistance
- Bonding/continuity checks
- Cell tower grounding verification
- Ground measurements on Railroad signaling systems
Statistics
ELECTRICAL GROUND RESISTANCE (AUTO-RANGING 1 TO 199Ω) MEASUREMENT RANGE:
|
0.010 to 0.099Ω, 0.10 to 0.99Ω, 1.0 to 49.9Ω, 50.0 to 99.5Ω, 100 to 199Ω, 200 to 395Ω, 400 to 590Ω, 600 to 1150Ω, 1200 to 1500Ω
|
ELECTRICAL RESOLUTION:
|
0.001Ω, 0.01Ω, 0.1Ω, 0.5Ω, 1Ω, 5Ω, 10Ω, 50Ω, 50Ω
|
ELECTRICAL ACCURACY (% OF READING):
|
±1.5% ±0.01Ω, ±1.5% ±0.02Ω, ±1.5% ±0.1Ω, ±2% ±0.5Ω, ±3% ±1Ω, ±5% ±5Ω, ±10% ±10Ω, 20% approx, 25% appro
|
ELECTRICAL CURRENT MEASUREMENT(AUTO-RANGING 1MA TO 40A) MEASUREMENT RANGE:
|
0.200 to 0.999mA, 1.000 to 2.990mA 3.00 to 9.99mA, 10.00 to 29.90mA 30.0 to 99.9mA, 100.0 to 299.0mA 0.300 to 0.990A, 1.000 to 2.990A 3.00 to 39.99A
|
ELECTRICAL RESOLUTION:
|
1µA, 10µA, 100µA, 1mA, 10mA
|
ELECTRICAL ACCURACY (% OF READING):
|
±2% ±50µA, ±2% ±50µA, ±2% ±100µA, ±2% ±1mA, ±2% ±10mA
|
ELECTRICAL SELECTABLE MEASUREMENT FREQUENCY:
|
50, 60, 128 or 2083Hz
|
ELECTRICAL CURRENT MEASUREMENT FREQUENCY:
|
47 to 800Hz
|
ELECTRICAL INDUCTANCE MEASUREMENT:
|
10 to 100µH; 100 to 500µH
|
ELECTRICAL CURRENT OVERLOAD:
|
OL displayed above 39.99Arms
|
ELECTRICAL COMMUNICATION:
|
Bluetooth connection (Model 6417 only)
|
ELECTRICAL POWER SOURCE:
|
4x1.5V LR6 (AA) Alkaline batteries or 4 NiMH batteries; Battery life: 12 hours, or 1440 30-second measurements approx
|
CALIFORNIA RESIDENTS:
WARNING Cancer and/or Reproductive Harm – see www.p65Warnings.ca.gov for more information