AEMC
AEMC 2137.57 PEL 105 Power and Energy Loggers
- SKU:
- 2137.57
- UPC:
- 6.85338E+11
- MPN:
- 2137.57
- Availability:
- 1 - 2 week lead time
- Weight:
- 10.00 LBS
- Shipping:
- Calculated at Checkout
Frequently bought together:
Description
AEMC 2137.57 PEL 105 Power and Energy Loggers
VISIT THE PEL SERIES WEBSITE: www.PEL100.us
Features
- Waterproof IP67 rated including the current sensors
- 5 voltage and 4 current measurement inputs
- Measures volts, amps, watts, VARs, kWh, power factor and harmonics out to the 50th
- Track energy costs including time of use
- Wi-Fi, Bluetooth Class 1, USB, LAN and Ethernet communication built in
- Powered from phase inputs up to 1000VAC or from a wall receptacle
- User selectable storage rates and demand intervals
- Pole mountable
- Can be configured directly from the front panel, through the DataView ® control panel or the free Android App
- Satisfies the recommendations of NEC 220.87
- Minimal programming required
- Automatic recognition of the connected current sensors/probes
Applications
- Measures efficiency and finds areas for potential savings
- Assign energy costs to departments or operations
- Track peak demand periods and find opportunities for surcharge reductions
- Determine present capacity and circumvent unnecessary electrical expansion costs
- Verify the reliability and operation of electrical machinery
- Improve response time to solve power related problems
- Track energy availability and reliability of supply
- Baseline studies for system upgrades in high-rise and office buildings
Statistics
GENERAL SAMPLING FREQUENCY:
|
128 samples per cycle; 50/60Hz (16 samples/cycle 400Hz)
|
GENERAL DATA STORAGE RATE:
|
samples per cycle; 50/60Hz (16 samples/cycle 400Hz) Data Storage Rate 1 per second (200ms also available on PEL 105)
|
GENERAL DEMAND PERIOD STORAGE RATE:
|
User selectable (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30 and 60 minutes)
|
GENERAL RECORDED PARAMETERS (SINGLE- AND POLY-PHASE):
|
V, I, W, VA, var, PF, Tan, Wh, VAh, varh, THD (V and I), Individual harmonics (from 1 through 50 per phase); Crest Factor (CF), Cos f / DPF
|
GENERAL EVENT LOG:
|
Tracks and records status changes and error messages along with recorded data
|
GENERAL FRONT PANEL INDICATOR LEDS:
|
Bluetooth active, recording in progress, phase connection reversal, overload, battery charging and SD Card status
|
GENERAL STORAGE CAPACITY:
|
SD card included / SD cards up to 32 GB formatted FAT32 are supported
|
INPUTS VOLTAGE:
|
PEL 102/103 3 input channels; PEL 105 4 input channels via 4mm safety banana jacks
|
INPUTS CURRENT:
|
PEL 102/103 - 3 current input channels ; PEL 105 4 input channels via custom 4 pin jacks that accept AEMC® probes and sensors
|
ELECTRICAL:
|
.
|
VOLTAGE MEASUREMENT/RESOLUTION/ACCURACY* 50/60HZ:
|
42.5 to 69Hz, ±0.1Hz
|
VOLTAGE MEASUREMENT/RESOLUTION/ACCURACY* SINGLE-PHASE RMS VOLTAGES:
|
10 to 1000Vrms, 0.1V/±0.2% Rdg ± 0.2V
|
VOLTAGE MEASUREMENT/RESOLUTION/ACCURACY* PHASE-TO-PHASE RMS VOLTAGES:
|
17 to 1000Vrms, 0.1 to 1V/±0.2% Rdg ± 0.4V
|
VOLTAGE MEASUREMENT/RESOLUTION/ACCURACY* 400HZ:
|
340 to 460Hz
|
VOLTAGE MEASUREMENT/RESOLUTION/ACCURACY* SINGLE-PHASE RMS VOLTAGES:
|
10 to 600Vrms, 0.1V/±1% Rdg ± 1V
|
VOLTAGE MEASUREMENT/RESOLUTION/ACCURACY* PHASE-TO-PHASE RMS VOLTAGES:
|
17 to 1200Vrms, 0.1 to 1V/±1% Rdg ± 1V
|
VOLTAGE MEASUREMENT/RESOLUTION/ACCURACY* DC:
|
10 to 1000V, 0.1V/±1% Rdg ± 3V (typical)
|
VOLTAGE MEASUREMENT/RESOLUTION/ACCURACY* PT RATIOS:
|
1% Rdg ± 3V (ty
|
CURRENT MEASUREMENT:
|
A193***, A196***
|
CURRENT MEASUREMENT NOMINAL RANGE FOR CURRENT PROBES SUPPLIED WITH KIT. SEE CHART ON PAGES 26 AND 27 FOR OTHER PROBES:
|
200mA to 3000Arms, 200mA to 10,000A
|
CURRENT MEASUREMENT CT RATIOS:
|
Programmable from 1:1 to 25,000:1 (probe dependent)
|
POWER MEASUREMENTS ACTIVE POWER (P)*:
|
0.001W, ±0.5% Rdg ± 0.005% Pnom
|
POWER MEASUREMENTS REACTIVE POWER (Q)*:
|
0.001var, m Reactive Power (Q)* -2 to 2Gvar 0.001var ±
|
POWER MEASUREMENTS APPARENT POWER (S)*:
|
0.001VA, ±0.5% Rdg ± 0.005% Snom
|
POWER MEASUREMENTS POWER FACTOR:
|
0.001, ± 0.05
|
POWER MEASUREMENTS TANGENT ? (ACTIVE/REACTIVE POWER RATIO):
|
0.001, ± 0.02
|
ENERGY MEASUREMENTS ACTIVE ENERGY (EP):
|
1Wh, ±0.5% Rdg
|
ENERGY MEASUREMENTS REACTIVE ENERGY (EQ):
|
1varh, ±2% Rdg
|
ENERGY MEASUREMENTS APPARENT ENERGY (ES):
|
1Vah, ±0.5% Rdg
|
THD:
|
± 655%
|
THD INDIVIDUAL HARMONICS:
|
1 to 50 displayed in percentage; 1 to 7 at 400Hz
|
THD EXTERNAL SUPPLY:
|
110V/250V (10%) @ 50/60Hz; 400Hz
|
THD POWER FROM PHASE MEASUREMENT:
|
PEL 102/103 requires optional Power Adapter Cat #2137.77; PEL 105 Internal up to 1000Vac
|
THD BACK-UP POWER SOURCE/CHARGE TIME:
|
Rechargeable 8.4V NiMH battery pack / Approximately 5 hours
|
THD BATTERY LIFE:
|
30 minutes minimum, 60 minutes typical
|
MECHANICAL COMMUNICATION PORTS:
|
USB 2.0, Ethernet (RJ45), Wireless Bluetooth Class 1 **/ Wi-Fi (PEL 105 only)
|
MECHANICAL DIMENSION/WEIGHT:
|
10.08 x 4.92 x 1.46 (256 x 125 x 37mm) / 2.20lbs (1kg) (PEL 102 & PEL 103)
|
9.8 X 7.8 X 2.6" (250 X 200 X 67MM) / 8.8LBS (4KG) (PEL 105)":
|
.
|
MECHANICAL CASE:
|
Double insulated, rubber over-molded, polycarbonate UL94 V1 rated
|
MECHANICAL MOUNTING/SECURITY:
|
Kensington anti-theft system (PEL 102 & PEL 103) / Embedded magnets on back side, keyhole slot on back side
|
DISPLAY:
|
.
|
DISPLAY DISPLAY TYPE FOR MODEL PEL 103 / PEL 105:
|
2.63 x 2.16 (67 x 55mm), four line, monochrome, backlit LCD with adjustable brightness and contrast"
|
ENVIRONMENTAL / SAFETY:
|
.
|
ENVIRONMENTAL / SAFETY STORAGE TEMPERATURE:
|
-4 to 122F (-20 to 50C) with batteries; -4 to 158F (-20 to 70C without batteries)
|
ENVIRONMENTAL / SAFETY SAFETY RATING/CE RATING:
|
Complies with IEC 61010-1:Ed3, and IEC 61010-2-030: Ed1 for 1000V CAT III / 600V CAT IV (PEL 102 & PEL 103) & 1000V CAT IV (PEL 105), Pollution Degree 2 / Yes
|
ENVIRONMENTAL / SAFETY INDEX OF PROTECTION:
|
IP54 non operating (PEL 102 & PEL 103) / IP67 with cover closed (PEL 105
|