AEMC 2136.5 DTR 8510 Motor Transformer Testers
The DTR ® Model 8510 is a portable digital transformer ratiometer designed for on-site testing of power, potential and current transformers. When connected to a non-energized transformer, the DTR ® Model 8510 accurately measures primary to secondary turns ratio, while simultaneously displaying polarity and excitation current. The DTR ® is fully automatic and uses an ANSI/IEEE compliant test method. No user calibration, range selection, hand cranking or tedious balancing is required. At each measurement, the DTR ® automatically self-calibrates and checks for open windings/connections/circuit breakers, short circuits (excess excitation current), incorrect test lead placement, and reverse polarity. Measurements are displayed quickly and accurately.
Features
- Ratio Testing: PT/VT from 0.8000:1 to 8000:1 and CT from 0.8000 to 1000.0 (Auto-Ranging)
- Tests performed by exciting the primary and reading the secondary; provides safer conditions for the operator on step-down transformers
- Continuity test indicates open or loose (high resistance) terminal connections
- DC test mode eliminates errors due to magnetic build up
- Stores up to 10 primary/secondary nameplate voltages to use in comparing test results
- Displays ratio, test current, winding polarity, and deviation from nameplate voltage or ratio
- Stores up to 10,000 test results
- DataView ® software included which allows configuring the instrument, downloading stored measurements and printing of test results in a report format
- Display warns of incorrect lead connection, reverse polarity, open and short circuits
Applications
- Power transformers
- Potential transformers
- Current transformers
Statistics
VT/PT RATIO RANGE:
|
Auto-Ranging 0.8000:1 to 8000:1
|
CT RATIO RANGE:
|
Auto-Ranging 0.8000 to 1000.0
|
ACCURACY*:
|
Ratio 1000 to 1: ±0.2% of Reading Ratio 5000 to 8000.0: ±0.25% of Reading
|
EXCITATION SIGNAL:
|
VT/PT Mode: 32Vrms maximum CT Mode: 0 to 1A, 0.1 to 4.5Vrms
|
EXCITATION CURRENT DISPLAY:
|
Range: 0 to 1000mA; Accuracy: ±2% of Reading ± 2mA
|
EXCITATION FREQUENCY:
|
70Hz
|
MEASUREMENT METHOD:
|
In accordance with ANSI/IEEE C57.12.90-2006
|
DISPLAY:
|
LCD 16 character, 2 line, large format, LED backlight, day/night visible
|
LANGUAGES SUPPORTED:
|
English, Spanish, French, Italian, German, Portuguese
|
COMMUNICATION:
|
Optically isolated USB 2.0
|
DATA STORAGE:
|
Stores up to 10,000 complete measurements
|
POWER SOURCE:
|
Two rechargeable 12V NiMH batteries (included)
|
EXTERNAL CHARGER:
|
90/240V, 50/60Hz (smart charger)
|
BATTERY LIFE:
|
Up to 10 hours continuous operation; May not be used while recharging; Low battery LED/LCD indication
|
CHARGING TIME:
|
<4 Hours
|